MCC DAQ

Block Catalogue / Devices

Acquires analogue inputs through the Measurement Computing Universal Library.

Input and output

Property Value
Type mccdaq, mc_daq, mcdaq
Inputs 1; see usage below
Consumes clock ticks
Publishes Vector<double> for one scan; Matrix<double> for multiple scans

Parameters

Index Parameter Type Default Meaning
0 Channels string 0;1;2;3;4;5;6;7 Semicolon-separated selection
1 ScansPerPacket int 10 At least one scan per tick
2 BoardNumber int 0 Configured board index
3 Range string Bip10Volts Device voltage range
4 Scale string volts volts or legacy

Requirements and use

Requires the official MCC DAQ Software/Universal Library on Windows. The public repository does not contain MccDaq.dll; supply it and build with -p:EnableMccDaq=true as described in Packages and optional devices. Without that opt-in build, the block remains visible but reports that the Universal Library is not installed.

Configure the board with InstaCal first, then start the Clock. The device scan rate is tick rate × scans per packet. Match downstream processing to the selected batch shape.

For parameter positions and connection rules, see Pipeline Configuration. For capturing output, see Recording.

Implementation

API reference. Model defaults above describe configuration loading; palette hints may expose a subset or select different defaults.

Search documentation