MCC DAQ
Block Catalogue / Devices
Acquires analogue inputs through the Measurement Computing Universal Library.
Input and output
| Property | Value |
|---|---|
| Type | mccdaq, mc_daq, mcdaq |
| Inputs | 1; see usage below |
| Consumes | clock ticks |
| Publishes | Vector<double> for one scan; Matrix<double> for multiple scans |
Parameters
| Index | Parameter | Type | Default | Meaning |
|---|---|---|---|---|
| 0 | Channels | string | 0;1;2;3;4;5;6;7 |
Semicolon-separated selection |
| 1 | ScansPerPacket | int | 10 | At least one scan per tick |
| 2 | BoardNumber | int | 0 | Configured board index |
| 3 | Range | string | Bip10Volts |
Device voltage range |
| 4 | Scale | string | volts |
volts or legacy |
Requirements and use
Requires the official MCC DAQ Software/Universal Library on Windows. The public
repository does not contain MccDaq.dll; supply it and build with
-p:EnableMccDaq=true as described in
Packages and optional devices. Without that
opt-in build, the block remains visible but reports that the Universal Library is not installed.
Configure the board with InstaCal first, then start the Clock. The device scan rate is tick rate × scans per packet. Match downstream processing to the selected batch shape.
For parameter positions and connection rules, see Pipeline Configuration. For capturing output, see Recording.
Implementation
API reference. Model defaults above describe configuration loading; palette hints may expose a subset or select different defaults.